18 Installation Guide THEIA HE-t String Inverters 357115.033, Issue 2.0, 2011 March
2.3.3.2. No Stringbox: Connector Panel
The connector panel is equipped with plug-in connectors or cable glands. A DC switch must
be installed separately by authorized personnel in compliance with the relevant national
electrical regulations.
Figure 2.3.12: Connector panel with optional DC
connectors
N1, N2, N3: Negative connectors
P1, P2, P3: Positive connectors
Figure 2.3.13: Customer connection area
P1’, P2’, P3’:
Terminals labeled +POS (Positive)
N1’, N2’, N3’:
Terminals labeled –NEG (Negative)
G1: DC ground terminal (See 2.3.2.
Grounding)
Negative grounded PV String
Connect the grounding strap between N3’ and G1.
With three strings, two of the string conductors must be connected to the same terminal, so
that the grounding strap has a terminal for itself.
Positive grounded PV String
Connect the grounding strap between P3’ and G1.
With three strings, two of the string conductors must be connected to the same terminal, so
that the grounding strap has a terminal for itself.